Application
| Environmental Space: | Indoor |
| Power Distribution Type: | Basic Standard |
Construction and Dimensions
| Rack Units: | 1U |
| Height: | 44 mm |
| Width: | 432 mm |
| Depth: | 165 mm |
Electrical Characteristics
| Input voltage: | 200-240 V |
| Rated Current*: | 32 A |
| Input frequency: | 50/60 Hz |
| Overcurrent Shut-Down: | (2) 16A Single Pole Magnetic Breakers |
| VA per Input (Load Capacity): | 7.3kW |
Mechanical Construction
| On-Off Switch: | Breaker/Switch Combination |
| Plug Type: | IEC60309 2P + E, 32A, 250V, Splashproof IP44 |
| Quantity Of Inputs: | 1 |
| Power Entry Location: | Front |
| Total Receptacle: | 12 |
| Receptacle 1 Type: | IEC C13 |
| Receptacle 1 Quantity: | 12 |
| Receptacle 1 Quantity per Breaker: | 6 |
| Receptacle 1 Style: | Banks of 3 |
| Receptacle 1 Voltage per Receptacle: | 230V |
| Receptacle 1 Maximum Output per Receptacle/Socket: | 10A per receptacle bank |
| Cord Length: | 3 m |
| Type of Cordage: | 4mm² H07RN-F |
Mechanical Characteristics
| Mounting: | Horizontal |
Environmental and Overall Characteristics
| Ambient Temperature (operation), max: | 45 |
| Finish: | Powder coat |
| Material: | Steel |
| Weight: | 3.63 kg |
Standards
| ISO/IEC Compliance: | IEC 60950-1 |
| EU CE Mark: | Yes |
| EU Directive 2011/65/EU (RoHS 2): | Compliant |
| CENELEC Compliance: | EN 55032, EN 55024 |
Related Part Numbers
| Part Number: | PDU-2810 |
| Packaging: | Individually boxed |
| Item # | Color |
|---|---|
| PDU-2810 | Black |
| Update and Revision: | Revision Number: 0.46 Revision Date: 03-30-2023 |