Product Overview
| Construction Type: | Central Loose Tube |
| Environmental Space: | Indoor/Outdoor – Euroclass Eca |
| Suitable Applications: | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and trenches and/or tubes. Suitable for Direct Burial. |
Construction
| Fiber Type | Fiber Count | Subunit Color |
|---|---|---|
| OM5 | 24 | TIA coding (Gxxxxxx.T): Natural |
| Fiber Color Coding: | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua. With Ringmark: BL, OR, GR, BR, GY, WT, RD, BK, YL, VT, PK, AQ |
| Cable Core Water Tight: | Yes |
| Cable Core Waterblocking: | Waterblocking Glass Yarns + Tape |
| Bulk Cable Weight: | 230 kg/km |
SubUnit Specifications
| Number of Active Subunits: | 1 |
| Number of Subunit Positions: | 1 |
| Fibers Per Subunit: | 24 |
| Subunit Diameter: | 4.2 mm |
| Subunit Waterblocking: | Gel Filled |
Jacket Specifications
| Number of Jackets: | Triple Jacket |
| Type of Armor: | Corrugated Steel Tape |
Outer Jacket Specifications
| Material | Nominal Diameter | Ripcord |
|---|---|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | No | |
| Nylon | ||
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | 13.6 mm |
| Table Notes: | Standard color: Black. Available colors: Black, Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Lime Green |
Optical Characteristics
| Max. Attenuation at 1300 nm: | 0.9 dB/km |
| Max. Attenuation at 850 nm: | 2.9 dB/km |
Mechanical Characteristics
| Description | Tested Standard | Requirement/Value | According to Family Specification |
|---|---|---|---|
| Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 272 mm | IEC 60794-3-10 |
| Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 136 mm | IEC 60794-3-10 |
| Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 5700 N (1281 lbf) | IEC 60794-3-10 |
| Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 1900 N (427 lbf) | IEC 60794-3-10 |
| Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 22 kN/m | IEC 60794-3-10 |
| Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 11 kN/m | IEC 60794-3-10 |
Temperature Range
| Operating Temperature Range: | -30 °C to +70 °C |
| Installation Temperature Range: | -5 °C to +40 °C |
| Storage Temperature Range: | -30 °C to +70 °C |
Standards
| UL Rating/Flame Test: | Non-UL Rated |
| IEC Flammability: | IEC 60332-1-2 |
| Reaction to Fire – Bundle Flame Test: | IEC 60332-3-22 |
| Resistance to Fire – Circuit Integrity: | IEC 60331-25-E120 |
| IEC 60754-1 – Halogen Amount: | Zero |
| IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: | 10 µS/mm |
| IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: | 4.3 |
| IEC 61034-2 – Smoke Density Min. Transmittance: | 60% |
| CPR Euroclass: | Eca |
| REACH: | Compliant |
| ISO/IEC Compliance: | IEC 60794-1-1 |
| EU Directive 2011/65/EU (RoHS 2): | Compliant |
| UV/ Sunlight Protection: | Yes |
History
| Update and Revision: | Revision Number: 0.44 Revision Date: 12-21-2023 |








































2 Port RJ45 Surface Mount Box White (Box only) SKU: ATDS101920WT
Snap-in Keystone Wallplate Blank Insert White SKU: ATDS101806WT
(Part Number - APC486048T22-h) - 48 X 60 X 48 Polymer Concrete Box & Cover - Tier 22 - OSP Handholes/Outside Plant Handholes
Duplex Adapter, 4P4C, Straight-Wired, White
Usb 2.0 Cable, Usb-A(M) To Usb-A(M), Beige, 3Ft