Product Overview
| Suitable Applications: | low voltage analog signals (4-20ma, 0-10v, …); low voltage digital control (24v, ); line level audio; computer communication; panel wiring |
Physical Characteristics (Overall)
| AWG | Stranding | Material | No. of Pairs |
|---|---|---|---|
| 18 | 16×30 | TC – Tinned Copper | 1 |
| Conductor Count: | 2 |
| Material | Nominal Diameter | Diameter +/- Tolerance |
|---|---|---|
| PE – Polyethylene | 2.08 mm | 0.05 mm |
| Number | Color |
|---|---|
| Pair 1 | Black & Clear |
| Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D |
|---|---|---|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | Beldfoil® | 100% | TC – Tinned Copper | 20 | 7×28 |
| Material | Color | Nominal Diameter | Nominal Wall Thickness |
|---|---|---|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 6.0 mm | 0.89 mm |
Electrical Characteristics
| Nominal Conductor DCR |
|---|
| 21.3 Ohm/km |
| Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
|---|---|
| 98 pF/m | 144 pF/m |
| Nominal Inductance |
|---|
| 0.591 µH/m |
| Element | Max. Recommended Current [A] |
|---|---|
| Conductor(s) | 5.2 Amps per Conductor at 25ºC |
| Voltage Rating [V] |
|---|
| 300 V |
Temperature Range
| Operating Temp Range (Flexible Install): | -15°C To +80°C |
| Operating Temp Range (Fixed Install): | -45°C To +80°C |
Mechanical Characteristics
| Oil Resistance: | IEC 60811-404 |
| Max. Pull Tension: | 280 N |
| Min. Bend Radius/Minor Axis: | 60 mm |
Standards
| CPR Euroclass: | B2ca-s1,d,1,a1 |
| CENELEC Compliance: | EN 50290-2-20 |
Applicable Environmental and Other Programs
| Environmental Space: | Indoor – Euroclass B2ca |
| EU Directive 2000/53/EC (ELV): | Yes |
| EU Directive 2003/96/EC (BFR): | Yes |
| EU Directive 2011/65/EU (RoHS 2): | Yes |
| EU Directive 2012/19/EU (WEEE): | Yes |
| EU CE Mark: | Yes |
Suitability
| Suitability – Indoor: | Yes |
| Suitability – Non-Halogenated: | Yes |
| Suitability – Sunlight Resistance: | Yes |
Flammability, LS0H, Toxicity Testing
| IEC Flammability: | IEC 60332-1-2 |
| IEC 60754-1 – Halogen Amount: | Zero |
| IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: | 2.5 µS/mm |
| IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: | 4.3 |
| IEC 61034-2 – Smoke Density Min. Transmittance: | 60% |
History
| Update and Revision: | Revision Number: 0.32 Revision Date: 02-15-2024 |