83569 – Electronic, 19 C #22 Str TC, FEP Ins, OS+TC Brd, FEP Jkt, CMP


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: extreme high/low temperature environments; chemical resistant; outdoor and burial applications; low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, …); line level audio; voice communications; panel wiring

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 19 22 AWG 7×30 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) FEP – Fluorinated Ethylene Propylene 0.007 in (0.18 mm) 0.042 in (1.1 mm) Black, White, Red, Green, Orange, Blue, White/Black Stripe, Red/Black Stripe, Green/Black Stripe, Orange/Black Stripe, Blue/Black Stripe, Black/White Stripe, Red/White Stripe, Green/White Stripe, Blue/White Stripe, Black/Red Stripe, White/Red Stripe, Orange/Red Stripe, Blue/Red Stripe
Outer Shield
Shield Type Material Coverage
Tape Bi-Laminate (Alum+Poly) 100%
Braid Tinned Copper (TC) 85%
Outer Jacket
Material Nom. Thickness Nom. Diameter
FEP – Fluorinated Ethylene Propylene 0.015 in (0.38 mm) 0.269 in (6.83 mm)
Overall Cable Diameter (Nominal): 0.269 in (6.83 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Max. Current
Conductor(s) 15.5 Ohm/1000ft 23 pF/ft (75 pF/m) 40 pF/ft (130 pF/m) 1.4 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V (CMP)

Mechanical Characteristics

Temperature
UL Temperature Operating
150°C -70°C to +200°C
Bend Radius
Stationary Min. Installation Min.
2.69 in (68.3 mm) 2.69 in (68.3 mm)
Max. Pull Tension: 225 lbs (102 kg)
Bulk Cable Weight: 81 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor – Plenum, Indoor, Outdoor, Sunlight Resistance, Oil Resistance
Sustainability: CA Prop 65
Flammability / Reaction to Fire: NFPA 262, UL 910 (Plenum), FT6
NEC / UL Compliance: Article 800, CMP
CEC / C(UL) Compliance: CMP
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

Product Notes

Notes: Gas Resistant

History

Update and Revision: Revision Number: 0.506 Revision Date: 11-27-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
83569 0021000 Red Reel 1,000 ft 612825205067 C

Select at least 2 products