7704ELW – LonWorks, 2PR #22 Sol BC, PO ins, OS, LSNH Jkt, 300V, Cca


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: LonWorks, instrumentation, Low capacitance

Physical Characteristics (Overall)

Conductor
AWG Stranding Material Nominal Diameter No. of Pairs
22 Solid BC – Bare Copper 0.64 mm 2
Conductor Count: 4
Total Number of Pairs: 2
Insulation
Material Nominal Diameter Min. Wall Thickness
PE – Polyethylene (Foam) 1.35 mm 0.3 mm
Color Chart
Number Color
Pair 1 White/Blue & Blue/White
Pair 2 Orange/White & White/Orange
Table Notes: Ring marking applied
Outer Shield
Type Material Coverage [%] Drainwire Material Drainwire Diameter Drainwire AWG
Tape Bi-Laminate (Alum+Poly) 100% TC – Tinned Copper 0.51 mm 24
Table Notes: Aluminum inside
Outer Jacket
Material Nominal Diameter Diameter +/- Tolerance Min. Wall Thickness
LSZH – Low Smoke Zero Halogen (Flame Retardant) 6.5 mm 0.4 mm 0.5 mm

Construction and Dimensions

Cabling
Description
2 pairs twisted to cable core

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR
55 Ohm/km 17 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Shield
40 pF/m 65 pF/m
Inductance
Nominal Pair Inductance
0.65 µH/m
Impedance
Frequency [MHz] Nominal Characteristic Impedance
1 – 20 100 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss Nom. NEXT [dB]
0.772 MHz 1.8 dB/100m
1 MHz 2 dB/100m 59 dB
4 MHz 3.6 dB/100m 50 dB
10 MHz 5.5 dB/100m 44 dB
16 MHz 7 dB/100m 41 dB
20 MHz 7.8 dB/100m 40 dB
Current
Element Max. Recommended Current [A]
Conductor(s) 2.5 Amps per Conductor
Voltage
Voltage Rating [V]
300 V

Temperature Range

Operating Temperature Range: -15°C To +80°C

Mechanical Characteristics

Bulk Cable Weight: 40.2 kg/km
Max. Pull Tension: 50 N
Min. Bend Radius During Installation: 80 mm

Standards

CPR Euroclass: Cca-s1,d1,a1

Applicable Environmental and Other Programs

Environmental Space: Indoor – Euroclass Cca

Flammability, LS0H, Toxicity Testing

IEC Flammability: IEC 60332-1-2
IEC 60754-1 – Halogen Amount: Zero

History

Update and Revision: Revision Number: 0.41 Revision Date: 02-15-2024

Select at least 2 products