6522UL – Fire Alarm, #22-4c BC, FPLP


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 22 AWG Solid BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC – Polyvinyl Chloride 0.01 in (0.25 mm) 0.046 in (1.2 mm) Black, Red, Brown, Blue
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.015 in (0.38 mm) 0.136 in Yes
Overall Cable Diameter (Nominal): 0.136 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
18.36 Ohm/1000ft 2.2 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C 0°C To +75°C
Bend Radius
Stationary Min. Installation Min.
1.08 in (27.4 mm) 1.08 in
Max. Pull Tension: 31.2 lbs (14.2 kg)
Bulk Cable Weight: 16 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: NFPA 262 (UL910)
NEC / UL Compliance: Article 760, FPLP
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): California State Fire Marshall
Non-Plenum Number: 5522UL

History

Update and Revision: Revision Number: 0.312 Revision Date: 05-05-2023

Part Numbers

Variants
Item # Color UPC
6522UL 0021000 Red 612825178170
6522UL 002U1000 Red 612825340423

Select at least 2 products
to compare