6222FL – Fire Alarm, #16-4c BC, Shielded, FPLP


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 16 AWG Solid BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC – Polyvinyl Chloride 0.01 in (0.25 mm) 0.071 in (1.8 mm) Black, Red, Brown, Blue
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 24 AWG (Solid) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.015 in (0.38 mm) 0.208 in Yes
Overall Cable Diameter (Nominal): 0.208 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Max. Current
4.18 Ohm/1000ft 43.5 pF/ft (143 pF/m) 78.3 pF/ft (257 pF/m) 5 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C 0°C To +75°C
Bend Radius
Stationary Min. Installation Min.
3.12 in (79.2 mm) 3.12 in
Max. Pull Tension: 130 lbs (59 kg)
Bulk Cable Weight: 51 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: NFPA 262 (UL910)
NEC / UL Compliance: Article 760, FPLP
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): California State Fire Marshall
Non-Plenum Number: 5222FL

History

Update and Revision: Revision Number: 0.316 Revision Date: 05-05-2023

Part Numbers

Variants
Item # Color UPC Footnote
6222FL 0021000 Red 612825174462 C

Select at least 2 products