Product Overview
| Suitable Applications: | Addressable Fire Systems, Data Circuits, Monitor/Detection, Control Circuits, Initiating Circuits, Notification Circuits |
Construction Details
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 4 | 16 AWG | 19×29 | TC – Tinned Copper |
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | PVC – Polyvinyl Chloride | 0.009 in (0.23 mm) | 0.077 in (2.0 mm) | Black, Red, White, Green |
| Material |
|---|
| No Shield |
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.216 in | Yes |
| Overall Cable Diameter (Nominal): | 0.216 in |
Electrical Characteristics
| Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
|---|---|---|
| 4.4 Ohm/1000ft | 36.5 pF/ft (120 pF/m) | 5 Amps per Conductor at 25ºC |
| UL Voltage Rating |
|---|
| 300 V |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 75°C | -20°C To +75°C |
| Stationary Min. | Installation Min. |
|---|---|
| 2.16 in (54.9 mm) | 2.16 in |
| Max. Pull Tension: | 114 lbs (51.7 kg) |
| Bulk Cable Weight: | 45 lbs/1000ft |
Standards and Compliance
| Environmental Suitability: | Indoor – Plenum, Indoor |
| Flammability / Reaction to Fire: | NFPA 262 (UL 910), FT6 |
| NEC / UL Compliance: | Article 800, CMP |
| CEC / C(UL) Compliance: | CMP |
| European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number: | 5202UH |
History
| Update and Revision: | Revision Number: 0.54 Revision Date: 11-23-2023 |
Part Numbers
| Item # | Color | Putup Type | Length | UPC |
|---|---|---|---|---|
| 6202UH 8771000 | Natural | Reel | 1,000 ft | 612825174264 |
| 6202UH 877U1000 | Natural | UnReel | 1,000 ft | 612825174677 |