6100FL – Fire Alarm, #14-2c BC, Shielded, FPLP


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 2 14 19×26 BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PVC – Polyvinyl Chloride 0.011 in (0.28 mm) 0.094 in (2.4 mm) Black, Red
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.015 in (0.38 mm) 0.218 in Yes

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Max. Current
2.67 Ohm/1000ft 78.5 pF/ft (258 pF/m) 141.25 pF/ft (463.42 pF/m) 25 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C 0°C To +75°C
Bend Radius
Stationary Min. Installation Min.
3.27 in (83.1 mm) 3.27 in
Max. Pull Tension: 104.1 lbs (47.22 kg)
Bulk Cable Weight: 38 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: NFPA 262 (UL910), IEC 60332-1-2
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 760, FPLP
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
APAC Compliance: China RoHS II (GB/T 26572-2011)
Non-Plenum Number: 5100FL

History

Update and Revision: Revision Number: 0.325 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color UPC Footnote
6100FL 0021000 Red 612825173342 C
6100FL 002U1000 Red 612825173335