Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 22 AWG Solid BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PO – Polyolefin 0.007 in (0.18 mm) 0.040 in (1.0 mm) Black and Red
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.017 in (0.43 mm) 0.114 in Yes
Overall Cable Diameter (Nominal): 0.114 in

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Pair(s) 18.4 Ohm/1000ft 2.8 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -20°C To +75°C
Bend Radius
Stationary Min. Installation Min.
0.91 in (23 mm) 0.91 in
Max. Pull Tension: 15.6 lbs (7.08 kg)
Bulk Cable Weight: 8 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: UL1666 Riser, FT4
NEC / UL Compliance: Article 760, FPLR

History

Update and Revision: Revision Number: 0.132 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color UPC
5520UL 0021000 Red 612825366669