5220UV – Fire Alarm, #16-2c BC, Low Capacitance, FPLR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Addressable Fire Alarm Circuits, SLC Loops, Initiating Devices, Digital Audio Loops

Construction Details

Conductor
Element No. of Pairs Size Stranding Material
Pair(s) 1 16 AWG Solid BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PP – Polypropylene .018 in (0.46 mm) .087 in (2.2 mm) Black, Red
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride .030 in (0.76 mm) .234 in (5.94 mm) Yes

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Characteristic Impedence Max. Current
3.9 Ohm/1000ft (13 Ohm/km) 14.5 pF/ft (47.6 pF/m) 100 Ohm 6.3 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -5°C To +75°C
Bend Radius
Stationary Min.
2.3 in (58 mm)
Max. Pull Tension: 62 lbs (28 kg)
Bulk Cable Weight: 35 lbs/1000ft (52 kg/km)

Standards and Compliance

Environmental Suitability: Indoor – Riser, Indoor
Flammability / Reaction to Fire: UL 1666 riser, IEC 60332-1-2
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 760, FPLR
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Plenum Number: 6220UJ

History

Update and Revision: Revision Number: 0.11 Revision Date: 02-21-2024

Select at least 2 products