Product Overview
| Suitable Applications: | Addressable Fire Alarm Circuits, SLC Loops, Initiating Devices, Digital Audio Loops |
Construction Details
| Element | No. of Pairs | Size | Stranding | Material |
|---|---|---|---|---|
| Pair(s) | 1 | 16 AWG | Solid | BC – Bare Copper |
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|
| PP – Polypropylene | .018 in (0.46 mm) | .087 in (2.2 mm) | Black, Red |
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | .030 in (0.76 mm) | .234 in (5.94 mm) | Yes |
Electrical Characteristics
| Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Max. Current |
|---|---|---|---|
| 3.9 Ohm/1000ft (13 Ohm/km) | 14.5 pF/ft (47.6 pF/m) | 100 Ohm | 6.3 Amps per Conductor at 25ºC |
| UL Voltage Rating |
|---|
| 300 V |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 75°C | -5°C To +75°C |
| Stationary Min. |
|---|
| 2.3 in (58 mm) |
| Max. Pull Tension: | 62 lbs (28 kg) |
| Bulk Cable Weight: | 35 lbs/1000ft (52 kg/km) |
Standards and Compliance
| Environmental Suitability: | Indoor – Riser, Indoor |
| Flammability / Reaction to Fire: | UL 1666 riser, IEC 60332-1-2 |
| CPR Compliance: | CPR Euroclass: Eca |
| NEC / UL Compliance: | Article 760, FPLR |
| European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
| Plenum Number: | 6220UJ |
History
| Update and Revision: | Revision Number: 0.11 Revision Date: 02-21-2024 |