3076F – Fieldbus, 1 Pr #18 Str TC, PP Ins, OS, PVC Jkt, Flexible SUN RES OIL RES, PLTC-ER, ITC-ER, CMX-Outdoor, CM


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: exposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 18 AWG 7×26 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PP – Polypropylene 0.022 in (0.56 mm) 0.088 in (2.2 mm) Blue & Orange
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.050 in (1.3 mm) 0.280 in (7.11 mm)
Table Notes: Jacket OD +/- 0.010
Overall Cable Diameter (Nominal): 0.280 in (7.11 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Capacitance Unbalance Nom. Capacitance Cond-to-Shield Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 7.2 Ohm/1000ft 1.2 pF/ft (3.9 pF/m) 45 pF/ft 100 Ohm 66% 5.2 Amps per Conductor at 25ºC
Nom. Outer Shield DCR: 8.5 Ohm/1000ft (28 Ohm/km)
High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 0.039 0.08 dB/100ft
High Frequency
Frequency [MHz] Max. Insertion Loss (Attenuation) Max./Min. Input Impedance (unFitted) [Ohm]
0.031 0.091 dB/100ft 100
Voltage
UL Voltage Rating
300 V (CM, PLTC-ER), 150 V (ITC-ER)

Mechanical Characteristics

Temperature
UL Temperature Operating
105°C -40°C to +105°C
Bend Radius
Stationary Min. Installation Min.
6.5 in (170 mm) 2.80 in (71.1 mm)
Max. Pull Tension: 60 lbs (27 kg)
Bulk Cable Weight: 44 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Oil Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, FT4, IEEE 1202, IEC 60332-1-2
CPR Compliance: CPR Euroclass: Eca; CPR UKCA Class: Eca
NEC / UL Compliance: Article 725, Article 727, Article 800, CMG, ITC, PLTC, TC
CEC / C(UL) Compliance: CMG
ISO/IEC Compliance: IEC 61158-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
Other Standard Compliance(s): ISA/SP-50 Type A

Product Notes

Notes: Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010

History

Update and Revision: Revision Number: 0.533 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
3076F 0061000 Blue, Light Reel 1,000 ft 612825140269 C
3076F 00310000 Orange 612825140214 C N
3076F 003250 Orange Reel 250 ft 612825140221 C
3076F 003500 Orange Reel 500 ft 612825140245 C
3076F 0031000 Orange Reel 1,000 ft 612825140207 C
3076F 0032500 Orange Reel 2,500 ft 612825140238 C
3076F 0035000 Orange Reel 5,000 ft 612825140252 C N

Select at least 2 products