29729C – VFD, 3C #1/0 Str BC XLPE Ins + #5 Symm. Seg. Gnd (3 of #10) Str BC, CTS, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements

Construction Details

Conductor
Element No. of Elements Size Stranding Material Notes
Conductor(s) 3 1/0 AWG 19×13 BC – Bare Copper
Ground 3 10 AWG 7×18 BC – Bare Copper Segmented Grounds
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.093 in (2.4 mm) 0.548 in (13.9 mm) Black and Numbered
Ground No Insulation
Outer Shield
Shield Type Material Coverage
Helical Tape Bare Copper (BC) 100%
Helical Tape Bare Copper (BC) 100%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 1.359 in (34.52 mm) Yes
Overall Cable Diameter (Nominal): 1.359 in (34.52 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 0.103 Ohm/1000ft (0.338 Ohm/km) 29 pF/ft (95 pF/m) 53 pF/ft (170 pF/m) 63 Ohm 55% 170 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
2000 V (TC), 1000 V (CSA AWM I/II A/B)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -40°C To +90°C
Bend Radius
Stationary Min. Installation Min.
16.3 in (414 mm) 16.3 in (414 mm)
Max. Pull Tension: 3958 lbs (1795 kg)
Bulk Cable Weight: 1528 lbs/1000ft (2274 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL Compliance: Article 336, TC-ER, RHW-2
AWM Compliance: I/II A/B
ICEA Compliance: S-95-658
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): P-07-KA070003-MSHA

History

Update and Revision: Revision Number: 0.69 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Putup Type UPC
29729C 0101000 Reel 612825445630
29729C 0101500 Reel 612825445647
29729C 0103000 Reel 612825445654
SKU: 29729C Categories: , , ,

Select at least 2 products