28119AS – TC VN/PVC, 12 C #12 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 12 12 AWG 7×20 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.019 in (0.48 mm) 0.131 in (3.33 mm) Brown, Red, Orange, Yellow, Blue, Black
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 12 AWG (7×20) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.676 in (17.2 mm) Yes
Overall Cable Diameter (Nominal): 0.676 in (17.2 mm)

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
1.7 Ohm/1000ft 15 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature
90°C Dry, 90°C Wet
Bend Radius
Stationary Min. Installation Min.
8.112 in (206.0 mm) 8.112 in (206.0 mm)
Max. Pull Tension: 1041.6 lbs (472.46 kg)
Bulk Cable Weight: 390 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, Article 310, TC-ER, THWN-2

History

Update and Revision: Revision Number: 0.56 Revision Date: 04-14-2023