27643AS – TC VN/PVC, 2 C #10 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 2 10 AWG 7×18 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.027 in (0.69 mm) 0.166 in mm Black, Red
Outer Shield
Shield Type Material Coverage
Tape Bi-Laminate (Alum+Poly) 100%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.048 in (1.2 mm) .432 in Yes
Overall Cable Diameter (Nominal): 0.432 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
1.06 Ohm/1000ft 40 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
5.184 in (131.7 mm) 5.184 in
Max. Pull Tension: 263.6 lbs (119.6 kg)
Bulk Cable Weight: 133 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
Plenum Number: ICEA S-73-532, S-95-658, S-61-402

History

Update and Revision: Revision Number: 0.199 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Putup Type UPC
27643AS 0105000 Reel 612825329770
27643AS 0105000 Reel 612825329770
27643AS01010000 Reel 612825329787

Select at least 2 products
to compare