189463 – Blue Hose®, 1 Pr #20 Str TC, PE Ins Blu, Clr, Foil+TC Braid Shld, PVC Jkt, CCA Armor, PVC Jkt, PLTC


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: exposure to rodent, crush, or cut through force, harsh environment, Allen Bradley Data Highway communication interface between PLC processors, I/O devices, operator interfaces, computers and other intelligent devices, PLC processor interlocking, peer-to-peer messaging, remote programming, troubleshooting, I/O updates, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 20 AWG 7×28 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Color Code Notes
Pair(s) PE – Polyethylene 0.019 in (0.48 mm) Clear & Blue Twinax with rod fillers
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC
Braid Tinned Copper (TC) 55%
Inner Jacket
Material Nom. Diameter
PVC – Polyvinyl Chloride 0.238 in (6.05 mm)
Armor
Armor Type & Material
CCAA – Continuously Corrugated Aluminum Armor
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.050 in (1.3 mm) 0.515 in (13.1 mm)
Overall Cable Diameter (Nominal): 0.515 in (13.1 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Shield Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop.
Pair(s) 9.5 Ohm/1000ft (31 Ohm/km) 19.7 pF/ft (64.6 pF/m) 37 pF/ft 36 pF/ft 78 Ohm 66%
Nom. Outer Shield DCR: 4.1 Ohm/1000ft (13 Ohm/km)
High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 1 0.6 dB/100ft
10 2.1 dB/100ft
50 5 dB/100ft
100 7.5 dB/100ft
200 11 dB/100ft
400 16 dB/100ft
Voltage
UL Voltage Rating
300 V (PLTC)

Mechanical Characteristics

Temperature
UL Temperature Operating
60°C -20°C to +60°C
Bend Radius
Stationary Min. Installation Min.
6 in (150 mm) 6 in
Max. Pull Tension: 205 lbs (93.0 kg)
Bulk Cable Weight: 121 lbs/1000ft (180 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL1685 UL Loading
NEC / UL Compliance: Article 725, PLTC
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
Other Standard Compliance(s): Allen Bradley Part No. 1770-CD

History

Update and Revision: Revision Number: 0.244 Revision Date: 02-15-2024

Select at least 2 products