1229530 – VFD 100% Gnd, 3C #2/0 Str TC XLPE Ins + #2/0 Symm. Seg. Gnd (3 of #4+) Str BC, CTS, PVC Jkt, AIA Armor, Blk PVC Jkt, 600V MC 90C Dry/Wet


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems; Exposure to rodents, crush or impact forces

Construction Details

Conductor
Element No. of Elements Size Stranding Material Notes
Conductor(s) 3 2/0 AWG 7x19x20 TC – Tinned Copper
Ground 3 4 AWG 7x19x25 BC – Bare Copper Segmented Grounds
Insulation
Element Material Nom. Thickness Color Code
Conductor(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.057 in (1.4 mm) Black and Numbered
Ground No Insulation
Outer Shield
Shield Type Material Coverage
Helical Tape Bare Copper (BC) 100%
Helical Tape Bare Copper (BC) 100%
Inner Jacket
Material Nom. Diameter
PVC – Polyvinyl Chloride 1.368 in (34.75 mm)
Armor
Armor Type & Material
AIA – Aluminum Interlock Armor
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 1.745 in (44.32 mm) Yes
Overall Cable Diameter (Nominal): 1.745 in (44.32 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 0.075 Ohm/1000ft (0.25 Ohm/km) 45 pF/ft (150 pF/m) 81 pF/ft (270 pF/m) 41 Ohm 55% 195 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (MC)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -25°C To +90°C
Bend Radius
Stationary Min. Installation Min.
20.9 in (531 mm) 20.9 in (531 mm)
Max. Pull Tension: 6543 lbs (2968 kg)
Bulk Cable Weight: 2561 lbs/1000ft (3811 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL Compliance: Article 336, MC, XHHW-2
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.72 Revision Date: 12-22-2023