PDU-12495 – PDU SW Unit Disp V Env Upg 230/400V 16A 3P+N+E (36)LC13


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Application

Features: Individual Outlet Switching with Optional User Defined Time Delays and Sequential Power-up
Environmental Space: Indoor
Power Distribution Type: Switched, Unit Level Monitored
Monitoring: Input power monitoring with Outlet switching. Circuit/Breaker current monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. Local high visibility LED display.
Input Monitoring: Total Unit Monitoring (kWh, W, VA, PF)
Circuit Monitoring: Circuit / Breaker Monitoring (A)
Environmental Monitoring: via optional remote sensors

Construction and Dimensions

Width: 51 mm
Depth: 66 mm
Length: 1683 mm

Electrical Characteristics

Input voltage: 200-240/346-415V WYE
Rated Current*: 16 A x 3 Phase WYE
Input frequency: 50/60 Hz
VA per Input (Load Capacity): 11.0 kW

Mechanical Construction

On-Off Switch: No
Plug Type: IEC60309 3P + N + E, 16A, 230/400V, Splashproof IP44
Quantity Of Inputs: 1
Power Entry Location: Bottom Front
Receptacle 1 Type: IEC C13 Locking
Receptacle 1 Quantity: 36
Receptacle 1 Style: Individual
Receptacle 1 Voltage per Receptacle: 230 V
Cord Length: 3 m
Type of Cordage: 2.5 mm^2 H07RN-F

Mechanical Characteristics

Mounting: Vertical
Toolless Mounting Hardware Center to Center Spacing: 1556mm and 1645mm

Environmental and Overall Characteristics

Network Connection: Dual 10/100Mbps Ethernet
Data Access Formats: CSV datalog, JSON API, JSON datalog.
• Protocols supported: DHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog, TACACS+
IP Reset Button: Yes
Hard Reboot Button: Yes
Remote Sensor RJ Connection Jacks: 1 (Supports up to 16 Sensors)
Ambient Temperature (operation), max: 45
Finish: Powder coat
Material: Steel
Color: Black
Weight: 8.2 kg

Standards

EU CE Mark: Yes
EU Directive 2011/65/EU (RoHS 2): Compliant
CENELEC Compliance: EN 55032, EN 55024

Related Part Numbers

Part Number: PDU-12495
Packaging: Individually boxed
Variants
Item # Color
PDU-12495 Black
Update and Revision: Revision Number: 0.10 Revision Date: 03-30-2023

Select at least 2 products