Product Overview
| Suitable Applications: | harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
Physical Characteristics (Overall)
| Element | AWG | Stranding | Material | No. of Conductors |
|---|---|---|---|---|
| Conductor(s) | 14 | 7×22 | BC – Bare Copper | 40 |
| Conductor Count: | 40 |
| Material | Nominal Diameter |
|---|---|
| PVC/Nylon – Polyvinyl Chloride + Nylon | 0.112 in |
| Number | Color |
|---|---|
| 1 | Black |
| 2 | Red |
| 3 | Blue |
| 4 | Orange |
| 5 | Yellow |
| 6 | Brown |
| 7 | Red/Black |
| 8 | Blue/Black |
| 9 | Orange/Black |
| 10 | Yellow/Black |
| 11 | Brown/Black |
| 12 | Black/Red |
| 13 | Blue/Red |
| 14 | Orange/Red |
| 15 | Yellow/Red |
| 16 | Brown/Red |
| 17 | Black/Blue |
| 18 | Red/Blue |
| 19 | Orange/Blue |
| 20 | Yellow/Blue |
| 21 | Brown/Blue |
| 22 | Black/Orange |
| 23 | Red/Orange |
| 24 | Blue/Orange |
| 25 | Yellow/Orange |
| 26 | Brown/Yellow |
| 27 | Black/Yellow |
| 28 | Red/Yellow |
| 29 | Blue/Yellow |
| 30 | Orange/Yellow |
| 31 | Brown/Yellow |
| 32 | Black/Brown |
| 33 | Red/Brown |
| 34 | Blue/Brown |
| 35 | Orange/Brown |
| 36 | Yellow/Brown |
| 37 | Black |
| 38 | Red |
| 39 | Blue |
| 40 | Orange |
| Material | Nominal Diameter | Nominal Wall Thickness |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.985 in | 0.083 in |
Electrical Characteristics
| Nominal Conductor DCR |
|---|
| 4.2 Ohm/1000ft |
| Max. Recommended Current [A] |
|---|
| 3.2 Amps per Conductor at 30ºC |
| UL Voltage Rating | Voltage Rating [V] |
|---|---|
| 600 V RMS (Type TC) | 600 V RMS (Type TC) |
Temperature Range
| UL Temp Rating: | 90°C Dry, 75°C Wet |
| Operating Temperature Range: | -25°C To +90°C |
Mechanical Characteristics
| UV Resistance: | Yes |
| Min Bend Radius (Overall): | 7.9 in |
| Min. Bend Radius/Minor Axis: | 3.94 in |
Standards
| NEC/(UL) Compliance: | TC-ER |
Applicable Environmental and Other Programs
| EU Directive 2000/53/EC (ELV): | Yes |
| EU Directive 2011/65/EU (RoHS 2): | Yes |
| EU Directive 2012/19/EU (WEEE): | Yes |
| EU Directive 2015/863/EU (RoHS 2 amendment): | Yes |
| EU Directive Compliance: | EU Directive 2003/11/EC (BFR) |
| EU CE Mark: | Yes |
Suitability
| Suitability – Burial: | Yes |
| Suitability – Indoor: | Yes |
| Suitability – Outdoor: | Yes |
| Suitability – Sunlight Resistance: | Yes |
Flammability, LS0H, Toxicity Testing
| UL Flammability: | UL1685 Vertical Tray Flame Test |
| IEEE Flammability: | 1202 |
| UL voltage rating: | 600 V RMS (Type TC) |
History
| Update and Revision: | Revision Number: 0.51 Revision Date: 01-10-2024 |