A03121W – TC VN/PVC, 3 C #12 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Physical Characteristics (Overall)

Conductor
Element AWG Stranding Material No. of Conductors
Conductor(s) 12 7×20 BC – Bare Copper 3
Conductor Count: 3
Insulation
Material Nominal Diameter
PVC/Nylon – Polyvinyl Chloride + Nylon 0.131 in
Color Chart
Number Color
1 Black
2 White
3 Red
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
PVC – Polyvinyl Chloride 0.385 in 0.047 in

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR
1.65 Ohm/1000ft
Current
Max. Recommended Current [A]
30 Amps per Conductor at 30ºC
Voltage
UL Description UL Voltage Rating Voltage Rating [V]
TC 600 V RMS (Type TC) 600 V RMS (Type TC)

Temperature Range

UL Temp Rating: 90°C Dry, 75°C Wet
Operating Temperature Range: -25°C To +90°C

Mechanical Characteristics

UV Resistance: Yes
Min Bend Radius (Overall): 3.85 in
Min. Bend Radius/Minor Axis: 1.54 in

Standards

NEC/(UL) Compliance: TC-ER, NPLF, THWN-2

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV): Yes
EU Directive 2011/65/EU (RoHS 2): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU (RoHS 2 amendment): Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
EU CE Mark: Yes

Suitability

Suitability – Burial: Yes
Suitability – Indoor: Yes
Suitability – Outdoor: Yes
Suitability – Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

UL Flammability: UL1685 Vertical Tray Flame Test
IEEE Flammability: IEEE 1202
UL voltage rating: 600 V RMS (Type TC)

Related Part Numbers

Variants
Item # Put-Up Type
A03121W 0105000 Reel

History

Update and Revision: Revision Number: 0.47 Revision Date: 09-05-2023

Select at least 2 products
to compare