9842LVS – RS-485, 2PR #24 Str TC, PO ins, F/B, LSNH Jkt, 300V, SWA, B2ca


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, …); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Physical Characteristics (Overall)

Conductor
AWG Stranding Material No. of Pairs
24 7×32 TC – Tinned Copper 2
Conductor Count: 4
Total Number of Pairs: 2
Insulation
Material Nominal Diameter Diameter +/- Tolerance
PE – Polyethylene 1.73 mm 0.05 mm
Color Chart
Number Color
Pair 1 White/Blue & Blue/White
Pair 2 White/Orange & Orange/White
Inner Shield
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG
Tape Bi-Laminate (Alum+Poly) Beldfoil® (Z-Fold®) TC – Tinned Copper AWG24/7
Braid Tinned Copper (TC) 100%
Inner Jacket
Material Color Nominal Diameter Nominal Wall Thickness
LSZH – Low Smoke Zero Halogen (Flame Retardant) Chrome (RAL 7037) 8.65 mm 1.1 mm
Table Notes: UV Stabilised
Outer Shield
Type Material Material Trade Name Drainwire Material
Tape Beldfoil® (Z-Fold®) TC – Tinned Copper
Braid Tinned Copper (TC)
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
LSZH – Low Smoke Zero Halogen (Flame Retardant) 13.1 mm 1.35 mm

Construction and Dimensions

Cabling
Description
2 pairs and 2 fillers twisted to cable core
Armor
Type of Armor Material Thickness of Armoring Wires Coverage Percentage
Steel Wire Armoring Galvanized steel wire 0.9 mm Min. 95%

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR
78.7 Ohm/km 7.2 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield
42 pF/m 75.5 pF/m
Impedance
Frequency [MHz] Nominal Characteristic Impedance
1 MHz 120 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss
1 MHz 1.97 dB/100m
Delay
Nominal Delay Nominal Velocity of Propagation (VP) [%]
520 ns/ft 66%
Current
Element Max. Recommended Current [A]
Conductor(s) 2.1 Amps per Conductor
Voltage
Voltage Rating [V]
300 V

Temperature Range

Installation Temperature Range: -15°C To +80°C
Storage Temperature Range: -45°C To +80°C
Operating Temp Range (Flexible Install): -15°C To +80°C
Operating Temp Range (Fixed Install): -45°C To +80°C

Mechanical Characteristics

Oil Resistance: IEC 60811-404
Min. Bend Radius During Installation: 196.5 mm

Standards

CPR Euroclass: B2ca-s1a,d1,a1
CENELEC Compliance: EN 50290-2-20
Other Specification: DMX-512

Applicable Environmental and Other Programs

Environmental Space: Indoor, Indoor/Outdoor, Outdoor, Indoor/Outdoor – Euroclass B2ca
EU CE Mark: Yes

Suitability

Suitability – Indoor: Yes
Suitability – Non-Halogenated: Yes
Suitability – Oil Resistance: Yes
Suitability – Outdoor: Yes
Suitability – Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

IEC Flammability: IEC 60332-1-2, IEC 60332-3-24
IEC 60754-1 – Halogen Amount: Zero
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: 2.5 µS/mm
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: 4.3
IEC 61034-2 – Smoke Density Min. Transmittance: 60%

Related Part Numbers

Variants
Item # Color Put-Up Type Length EAN
9842LVS.001000 Black Reel 1,000 m 8719605176219

History

Update and Revision: Revision Number: 0.58 Revision Date: 02-20-2024

Select at least 2 products