Product Overview
| Suitable Applications: | LonWorks, instrumentation, Low capacitance |
Physical Characteristics (Overall)
| AWG | Stranding | Material | Nominal Diameter | No. of Pairs |
|---|---|---|---|---|
| 22 | Solid | BC – Bare Copper | 0.64 mm | 2 |
| Conductor Count: | 4 |
| Total Number of Pairs: | 2 |
| Material | Nominal Diameter | Min. Wall Thickness |
|---|---|---|
| PE – Polyethylene (Foam) | 1.35 mm | 0.3 mm |
| Number | Color |
|---|---|
| Pair 1 | White/Blue & Blue/White |
| Pair 2 | Orange/White & White/Orange |
| Table Notes: | Ring marking applied |
| Type | Material | Coverage [%] | Drainwire Material | Drainwire Diameter | Drainwire AWG |
|---|---|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | TC – Tinned Copper | 0.51 mm | 24 |
| Table Notes: | Aluminum inside |
| Material | Nominal Diameter | Diameter +/- Tolerance | Min. Wall Thickness |
|---|---|---|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | 6.5 mm | 0.4 mm | 0.5 mm |
Construction and Dimensions
| Description |
|---|
| 2 pairs twisted to cable core |
Electrical Characteristics
| Nominal Conductor DCR | Nominal Outer Shield DCR |
|---|---|
| 55 Ohm/km | 17 Ohm/km |
| Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Shield |
|---|---|
| 40 pF/m | 65 pF/m |
| Nominal Pair Inductance |
|---|
| 0.65 µH/m |
| Frequency [MHz] | Nominal Characteristic Impedance |
|---|---|
| 1 – 20 | 100 Ohm |
| Frequency [MHz] | Nom. Insertion Loss | Nom. NEXT [dB] |
|---|---|---|
| 0.772 MHz | 1.8 dB/100m | |
| 1 MHz | 2 dB/100m | 59 dB |
| 4 MHz | 3.6 dB/100m | 50 dB |
| 10 MHz | 5.5 dB/100m | 44 dB |
| 16 MHz | 7 dB/100m | 41 dB |
| 20 MHz | 7.8 dB/100m | 40 dB |
| Element | Max. Recommended Current [A] |
|---|---|
| Conductor(s) | 2.5 Amps per Conductor |
| Voltage Rating [V] |
|---|
| 300 V |
Temperature Range
| Operating Temperature Range: | -15°C To +80°C |
Mechanical Characteristics
| Bulk Cable Weight: | 40.2 kg/km |
| Max. Pull Tension: | 50 N |
| Min. Bend Radius During Installation: | 80 mm |
Standards
| CPR Euroclass: | Cca-s1,d1,a1 |
Applicable Environmental and Other Programs
| Environmental Space: | Indoor – Euroclass Cca |
Flammability, LS0H, Toxicity Testing
| IEC Flammability: | IEC 60332-1-2 |
| IEC 60754-1 – Halogen Amount: | Zero |
History
| Update and Revision: | Revision Number: 0.41 Revision Date: 02-15-2024 |