Product Overview
| Suitable Applications: | Access Control, Security System, Power Limited Controls |
Construction Details
| Element Description | Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|---|
| Card Reader | Pair(s) | 3 | 18 AWG | 7×26 | BC – Bare Copper |
| Door Contact | Conductor(s) | 2 | 18 AWG | 7×26 | BC – Bare Copper |
| REX/Spare | Conductor(s) | 4 | 18 AWG | 7×26 | BC – Bare Copper |
| Lock Power | Conductor(s) | 4 | 16 AWG | 19×29 | BC – Bare Copper |
| Element Description | Element | Material | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Card Reader | Pair(s) | PVC – Polyvinyl Chloride | Black & Red, White & Green, Brown & Orange | |
| Door Contact | Conductor(s) | PVC – Polyvinyl Chloride | Black, Red | |
| REX/Spare | Conductor(s) | PVC – Polyvinyl Chloride | Black, Red, White, Green | |
| Lock Power | Conductor(s) | PVC – Polyvinyl Chloride | 0.075 in (1.9 mm) |
| Element Description | Element | Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|---|---|
| Card Reader | Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
| Door Contact | Conductor(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
| REX/Spare | Conductor(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
| Lock Power | Conductor(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
| Element Description | Element | Material | Nom. Diameter | Ripcord | Color |
|---|---|---|---|---|---|
| Card Reader | Pair(s) | PVC – Polyvinyl Chloride | 0.288 in (7.32 mm) | Yes | Orange |
| Door Contact | Conductor(s) | PVC – Polyvinyl Chloride | 0.168 in (4.27 mm) | Yes | White |
| REX/Spare | Conductor(s) | PVC – Polyvinyl Chloride | 0.197 in (5.00 mm) | Yes | Blue |
| Lock Power | Conductor(s) | PVC – Polyvinyl Chloride | 0.224 in (5.69 mm) | Yes | Gray |
| Material | Nom. Diameter | Ripcord |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.582 in (14.8 mm) | Yes |
| Overall Cable Diameter (Nominal): | 0.582 in (14.8 mm) |
Electrical Characteristics
| Element Description | Element | Nom. Conductor DCR | Nom. Inner Shield DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Shield | Max. Current |
|---|---|---|---|---|---|---|
| Card Reader | Pair(s) | 6.6 Ohm/1000ft (22 Ohm/km) | 13.1 Ohm/1000ft (43.0 Ohm/km) | 40 pF/ft (130 pF/m) | 72 pF/ft (240 pF/m) | 4 Amps per Conductor at 25ºC |
| Door Contact | Conductor(s) | 6.6 Ohm/1000ft (22 Ohm/km) | 16.7 Ohm/1000ft (54.8 Ohm/km) | 70 pF/ft (230 pF/m) | 126 pF/ft (413 pF/m) | 4 Amps per Conductor at 25ºC |
| REX/Spare | Conductor(s) | 6.6 Ohm/1000ft (22 Ohm/km) | 15.9 Ohm/1000ft (52.2 Ohm/km) | 42 pF/ft (140 pF/m) | 76 pF/ft (250 pF/m) | 4 Amps per Conductor at 25ºC |
| Lock Power | Conductor(s) | 4 Ohm/1000ft (13 Ohm/km) | 15.9 Ohm/1000ft (52.2 Ohm/km) | 45 pF/ft (150 pF/m) | 81 pF/ft (270 pF/m) | 5 Amps per Conductor at 25ºC |
| UL Voltage Rating |
|---|
| 300 V (UL CMP) |
Mechanical Characteristics
| Operating |
|---|
| 0°C to +75°C |
| Max. Pull Tension: | 253 lbs (115 kg) |
| Bulk Cable Weight: | 181 lbs/1000ft (269 kg/km) |
Standards and Compliance
| Environmental Suitability: | Indoor – Plenum, Indoor |
| Flammability / Reaction to Fire: | NFPA 262 |
| NEC / UL Compliance: | Article 800, CMP |
| CEC / C(UL) Compliance: | CMP |
| European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number: | 538AFJ |
History