62P1816 – Inst, 16 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …), encoders, control circuits, distributed control

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 16 18 AWG 7×26 BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PVC/Nylon – Polyvinyl Chloride + Nylon 0.016 in (0.41 mm) 0.088 in (2.2 mm) ICEA Chart E1
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Each Pair Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 0.931 in Yes

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Inner Shield DCR Max. Current
6.79 Ohm/1000ft 2.08 Ohm/1000ft (6.82 Ohm/km) 6 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 75°C Wet -30°C To +90°C Dry, +75°C Wet
Bend Radius
Stationary Min. Installation Min.
3.72 in (94.5 mm) 4.65 in
Max. Pull Tension: 871.5 lbs (395.3 kg)
Bulk Cable Weight: 430 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, Article 760
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

Product Notes

Notes: Alternate color coding available upon request.

History

Update and Revision: Revision Number: 0.53 Revision Date: 01-10-2024

Part Numbers

Variants
Item # Putup Type UPC
62P1816 0105000 Reel 612825360254

Select at least 2 products