Product Overview
| Suitable Applications: | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, ), encoders, control circuits, distributed control |
Construction Details
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Pair(s) | 24 | 18 | 7×26 | BC – Bare Copper |
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|
| PVC/Nylon – Polyvinyl Chloride + Nylon | 0.016 in (0.41 mm) | 0.088 in (2.2 mm) | ICEA Chart E1 |
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | 0.084 in (2.1 mm) | 1.017 in (25.83 mm) | Yes |
Electrical Characteristics
| Nom. Conductor DCR | Max. Current |
|---|---|
| 6.79 Ohm/1000ft | 5 Amps per Conductor at 25ºC |
| UL Voltage Rating |
|---|
| 600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 90°C Dry, 75°C Wet | -30°C To +90°C Dry, +75°C Wet |
| Stationary Min. | Installation Min. |
|---|---|
| 5.05 in (128 mm) | 5.05 in (128 mm) |
| Max. Pull Tension: | 1075.2 lbs (487.70 kg) |
| Bulk Cable Weight: | 524 lbs/1000ft |
Standards and Compliance
| Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
| Flammability / Reaction to Fire: | UL 1685 UL loading, IEEE 1202 FT4 |
| NEC / UL Compliance: | Article 336, Article 760, NPLF, TC-ER |
History
| Update and Revision: | Revision Number: 0.56 Revision Date: 01-04-2024 |