Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 12 18 AWG Solid BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PP – Polypropylene 0.007 in (0.18 mm) 0.055 in (1.4 mm) Black, Red, Brown, Blue, Orange, Yellow, Purple, Green, Red/Black, Red/White, Red/Green, Red/Blue
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.018 in (0.46 mm) 0.262 in Yes
Overall Cable Diameter (Nominal): 0.262 in

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Max. Current
Conductor(s) 6.4 Ohm/1000ft 22 pF/ft (72 pF/m) 3.5 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -20°C To +75°C
Bend Radius
Stationary Min. Installation Min.
2.09 in (53.1 mm) 2.09 in
Max. Pull Tension: 235.2 lbs (106.7 kg)
Bulk Cable Weight: 73 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: UL1666 Riser
NEC / UL Compliance: Article 760, FPLR
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): California State Fire Marshall

History

Update and Revision: Revision Number: 0.306 Revision Date: 05-05-2023

Part Numbers

Variants