, , , , , , ,

5222FL – Fire Alarm, #16-4c BC, Shielded, FPLR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 16 Solid BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PP – Polypropylene 0.007 in (0.18 mm) 0.065 in (1.7 mm) Black, Red, Brown, Blue
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.017 in (0.43 mm) 0.197 in Yes

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Max. Current
4.18 Ohm/1000ft 32.5 pF/ft (107 pF/m) 58.5 pF/ft (192 pF/m) 5 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -20°C To +75°C
Bend Radius
Stationary Min. Installation Min.
2.95 in (74.9 mm) 2.95 in
Max. Pull Tension: 124.8 lbs (56.61 kg)
Bulk Cable Weight: 43 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor
Flammability / Reaction to Fire: UL 1666 riser
NEC / UL Compliance: Article 760, FPLR
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): California State Fire Marshall
Plenum Number: 6222FL

History

Update and Revision: Revision Number: 0.321 Revision Date: 05-05-2023

Part Numbers

Variants
Item # Color UPC
5222FL 0021000 Red 612825158523

Select at least 2 products
to compare