Product Overview
| Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 3 | 18 AWG | 7×26 | BC – Bare Copper |
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.088 in mm | Black, White, Red |
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7×28) TC |
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.290 in | Yes |
| Overall Cable Diameter (Nominal): | 0.290 in |
Electrical Characteristics
| Nom. Conductor DCR | Max. Current |
|---|---|
| 6.66 Ohm/1000ft | 14 Amps per Conductor at 30ºC |
| UL Voltage Rating |
|---|
| 600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 90°C Dry, 90°C Wet | Wet/Dry: -30°C To +90°C |
| Stationary Min. | Installation Min. |
|---|---|
| 3.48 in (88.4 mm) | 3.48 in |
| Max. Pull Tension: | 79.8 lbs (36.2 kg) |
| Bulk Cable Weight: | 48 lbs/1000ft |
Standards and Compliance
| Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
| Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance: | Article 336, Article 760, TC-ER, NPLF, TFFN |
| European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision: | Revision Number: 0.58 Revision Date: 06-07-2023 |
Part Numbers
| Item # | Putup Type |
|---|---|
| 48334AS 0085000 | Reel |
| 48334AS 0105000 | Reel |
| 48334AS01010000 | Reel |