47109A – TC VN/PVC, 2 C #12 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 2 12 AWG 7×20 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.021 in (0.53 mm) 0.134 in mm Black, White
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.048 in (1.2 mm) 0.372 in x 0.234 in Yes
Overall Cable Diameter (Nominal): 0.372 in x 0.234 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
1.65 Ohm/1000ft 30 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 75°C Wet Wet/Dry: -30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
0.936 in (23.8 mm) 1.17 in
Max. Pull Tension: 173.6 lbs (78.74 kg)
Bulk Cable Weight: 74 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, Article 760, NPLF, TC, THHN, THWN
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.59 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Putup Type
47109A 0105000 Reel

Select at least 2 products