| Suitable Applications: | Variable Frequency Drives (VFD); AC Motor and Drive Systems; Specific ratings for applications in Canada |
Construction Details
| Element | No. of Elements | Size | Stranding | Material | Notes |
|---|---|---|---|---|---|
| Conductor(s) | 3 | 3/0 AWG | 19×10 | BC – Bare Copper | |
| Ground Wire | 3 | 8 AWG | 7×16 | BC – Bare Copper | Segmented Grounds |
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLPE – Cross-Linked Polyethylene (Thermoset) | 0.080 in (2.0 mm) | 0.622 in (15.8 mm) | ICEA Chart M4 |
| Ground Wire | No Insulation |
| Shield Type | Material | Coverage |
|---|---|---|
| Tape | Polypropylene Foam | 100% |
| Helical Tape | Bare Copper (BC) | 100% |
| Helical Tape | Bare Copper (BC) | 100% |
| Table Notes: | Separator-Polypropylene Tape |
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | 0.093 in (2.4 mm) | 1.553 in (39.45 mm) | Yes |
| Overall Cable Diameter (Nominal): | 1.553 in (39.45 mm) |
Electrical Characteristics
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|---|
| Conductor(s) | 0.065 Ohm/1000ft | 33 pF/ft (110 pF/m) | 60 pF/ft (200 pF/m) | 56 Ohm | 55% | 225 Amps per Conductor at 30ºC |
| 0.68 Ohm/1000ft (2.2 Ohm/km) | 55 Amps per Conductor at 25ºC |
| UL Voltage Rating | Voltage Rating |
|---|---|
| 1000 V (CSA TC) | 1000 V (CSA TC) |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 90°C Dry, 90°C Wet | -40°C To +90°C |
| Stationary Min. | Installation Min. |
|---|---|
| 18.7 in (475 mm) | 18.7 in (475 mm) |
| Max. Pull Tension: | 6716 lbs (3046 kg) |
| Bulk Cable Weight: | 2273 lbs/1000ft |
Standards and Compliance
| Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
| Sustainability: | CA Prop 65 |
| Flammability / Reaction to Fire: | UL 1685 UL Loading |
| CEC / C(UL) Compliance: | CSA TC |
| ICEA Compliance: | S-95-658 |
| European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision: | Revision Number: 0.379 Revision Date: 12-22-2023 |