29530F – VFD 100% Gnd, 3C #2/0 Str TC XLPE Ins + #2/0 Symm. Seg. Gnd (3 of #4+) Str TC, CTS, Blk TPE Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems, Exposure to high flex, motion, and abrasion, Hard to reach installation areas

Construction Details

Conductor
Element No. of Elements Size Stranding Material Notes
Conductor(s) 3 2/0 AWG 7x7x27x30 TC – Tinned Copper
Ground 3 4 AWG 7x60x30 TC – Tinned Copper Segmented Grounds
Insulation
Element Material Nom. Thickness Color Code
Conductor(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.057 in (1.4 mm) Black and Numbered
Ground No Insulation
Outer Shield
Shield Type Material Coverage
Helical Tape Bare Copper (BC) 100%
Helical Tape Bare Copper (BC) 100%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
TPE – Thermoplastic Elastomer 0.083 in (2.1 mm) 1.503 in (38.18 mm) Yes
Overall Cable Diameter (Nominal): 1.503 in (38.18 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 0.077 Ohm/1000ft (0.25 Ohm/km) 50 pF/ft (160 pF/m) 90 pF/ft (300 pF/m) 36 Ohm 55% 195 Amps per Conductor at 30ºC (per NEC)
Voltage
UL Voltage Rating
1000 V (TC, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -40°C To +90°C
Bend Radius
Stationary Min. Installation Min. Flexing Min.
7.5 in (190 mm) 18.0 in (457 mm) 18.0 in (457 mm)
Max. Pull Tension: 6797 lbs (3083 kg)
Bulk Cable Weight: 2080 lbs/1000ft (3100 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL1685 UL Loading, FT4, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL Compliance: Article 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) Compliance: CIC, TC
ICEA Compliance: S-95-658
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.399 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type UPC
29530F 0102000 Black Reel 612825373407

Select at least 2 products
to compare