28177A – TC VN/PVC, 3+G C #4/0+4 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 4/0 19×10 BC – Bare Copper
Ground 1 4 7×12 BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PVC/Nylon – Polyvinyl Chloride + Nylon 0.054 in (1.4 mm) 0.621 in (15.8 mm) Black and Numbered
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 1.543 in (39.19 mm) Yes

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Conductor(s) 0.052 Ohm/1000ft 260 Amps per Conductor at 30ºC
Ground 0.26 Ohm/1000ft (0.85 Ohm/km) 95 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet Wet/Dry: -30°C to 90°C
Bend Radius
Stationary Min. Installation Min.
7.7 in (200 mm) 7.7 in (200 mm)
Max. Pull Tension: 8017.6 lbs (3636.7 kg)
Bulk Cable Weight: 2525 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC-ER, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and Revision: Revision Number: 0.78 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Putup Type UPC
28177A 0102500 Reel 612825365686

Select at least 2 products