28160A – TC VN/PVC, 4+G C #2+6 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 2 7×10 BC – Bare Copper
Ground 1 6 7×14 BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PVC/Nylon – Polyvinyl Chloride + Nylon 0.042 in (1.1 mm) 0.367 in (9.32 mm) Black and Numbered
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 1.106 in (28.09 mm) Yes

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Conductor(s) 0.16 Ohm/1000ft 104 Amps per Conductor at 30ºC
Ground 0.4 Ohm/1000ft (1.3 Ohm/km) 78 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
600 V (TC-ER)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet Wet/Dry: -30°C to 90°C
Bend Radius
Stationary Min. Installation Min.
5.5 in (140 mm) 5.5 in (140 mm)
Max. Pull Tension: 3496.3 lbs (1585.9 kg)
Bulk Cable Weight: 1211 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC-ER, THWN-2 Singles
European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.546 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
28160A 0105000 Black Reel 5,000 ft 612825135630 C Z

Select at least 2 products