2127A – Fieldbus, 1 Pr #16 Str TC, XLPE Ins, OS, TPE Jkt, 600V TC


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 16 AWG 7×24 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.038 in (0.97 mm) 0.135 in (3.43 mm) Blue, Orange and Numbered
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7×26) TC
Outer Jacket
Separator Material Nom. Thickness Nom. Diameter Ripcord
Polyester Tape TPE – Thermoplastic Elastomer 0.047 in (1.2 mm) 0.374 in (9.50 mm) Yes
Overall Cable Diameter (Nominal): 0.374 in (9.50 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Capacitance Unbalance Nom. Capacitance Cond-to-Shield Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 4.5 Ohm/1000ft 1.2 pF/ft (3.9 pF/m) 22 pF/ft 100 Ohm 64% 11.6 Amps per Conductor at 25ºC
Nom. Outer Shield DCR: 5.1 Ohm/1000ft (17 Ohm/km)
High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 0.039 0.065 dB/100ft
High Frequency
Max. Insertion Loss (Attenuation) Max./Min. Input Impedance (unFitted) [Ohm]
0.091 dB/100ft 100
Voltage
UL Voltage Rating
600 V

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C -40°C to +90°C Wet/Dry
Table Notes: -40C
Bend Radius
Stationary Min. Installation Min.
3.75 in (95.3 mm) 3.75 in (95.3 mm)
Max. Pull Tension: 93 lbs (42 kg)
Bulk Cable Weight: 67 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Flammability / Reaction to Fire: UL 1581 Vertical Tray, FT4, IEEE 1202, IEC 60332-3-24
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 336, ITC, PLTC
AWM Compliance: AWM I/II A/B
CEC / C(UL) Compliance: CIC, TC
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
Other Standard Compliance(s): ISA/SP-50 Type A

History

Update and Revision: Revision Number: 0.559 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color Putup Type Length UPC
2127A 0061000 Blue, Light Reel 1,000 ft 612825129943
2127A 0065000 Blue, Light Reel 5,000 ft 612825129950
2127A 0035000 Orange Reel 5,000 ft 612825129936

Select at least 2 products