Product Overview
| Suitable Applications: | exposure to rodent, crush, or cut through force, burial, POS, serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, outdoor such as solar, lighting, etc. |
Construction Details
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Pair(s) | 1 | 24 AWG | 7×32 | TC – Tinned Copper |
| Element | Material | Nom. Thickness | Color Code |
|---|---|---|---|
| Pair(s) | PE – Polyethylene | 0.023 in (0.58 mm) | White/Blue Stripe & Blue/White Stripe |
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
| Braid | Tinned Copper (TC) | 90% |
| Material | Nom. Thickness | Nom. Diameter |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.035 in (0.89 mm) | 0.232 in (5.89 mm) |
| Armor Type & Material |
|---|
| AIA – Aluminum Interlock Armor |
| Material | Nom. Thickness | Nom. Diameter |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.045 in (1.1 mm) | 0.512 in (13.0 mm) |
| Overall Cable Diameter (Nominal): | 0.512 in (13.0 mm) |
Electrical Characteristics
| Element | Nom. Characteristic Impedence | Max. Current |
|---|---|---|
| Pair(s) | 120 Ohm | 2.1 Amps per Conductor at 25ºC |
| Element | Frequency [MHz] |
|---|---|
| Pair(s) | 1 |
| UL Voltage Rating |
|---|
| 300 V (CM) |
Mechanical Characteristics
| UL Temperature |
|---|
| 80°C |
| Table Notes: | -40C CSA |
| Max. Pull Tension: | 200 lbs (91 kg) |
| Bulk Cable Weight: | 126 lbs/1000ft (188 kg/km) |
Standards and Compliance
| Environmental Suitability: | Outdoor, Sunlight Resistance |
| Flammability / Reaction to Fire: | UL1685 UL Loading |
| NEC / UL Compliance: | Article 800, CM |
| CEC / C(UL) Compliance: | CMG |
History
| Update and Revision: | Revision Number: 0.114 Revision Date: 02-15-2024 |