Product Overview
| Suitable Applications: | MIL-W-16878 (Type B) Spec; up to 600V analog signals ; up to 600V voltage control |
Construction Details
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 2 | 22 | 19×34 | TC – Tinned Copper |
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|
| PVC/Nylon – Polyvinyl Chloride + Nylon | 0.0125 in (0.318 mm) | 0.056 in (1.4 mm) | White, Black |
| Nylon | 0.003 in (0.076 mm) |
| Shield Type | Material | Coverage |
|---|---|---|
| Braid | Tinned Copper (TC) | 92% |
| Material | Nom. Thickness | Nom. Diameter |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.02 in (0.51 mm) | 0.174 in (4.42 mm) |
Electrical Characteristics
| Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
|---|---|---|---|
| 14.6 Ohm/1000ft | 52 pF/ft (170 pF/m) | 87 pF/ft (290 pF/m) | 2.8 Amps per Conductor at 25ºC |
| Voltage Rating |
|---|
| 600 V |
Mechanical Characteristics
| UL Temperature | Operating |
|---|---|
| 105°C | -20°C To +105°C |
| Stationary Min. | Installation Min. |
|---|---|
| 1.74 in (44.2 mm) | 1.74 in (44.2 mm) |
| Max. Pull Tension: | 19 lbs (8.6 kg) |
| Bulk Cable Weight: | 19 lbs/1000ft |
Standards and Compliance
| Flammability / Reaction to Fire: | IEC 60332-1-2 |
| CPR Compliance: | CPR Euroclass: Eca |
| Military Compliance: | MIL-W-16878E/17 (insulated conductor) |
| European Directive Compliance: | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK Regulation Compliance: | UKCA Mark |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision: | Revision Number: 0.498 Revision Date: 02-15-2024 |
Part Numbers
| Item # | Color | UPC | Footnote |
|---|---|---|---|
| 9966 009100 | White | 612825265313 | |
| 9966 0091000 | White | 612825265320 | C |
| 9966 009500 | White | 612825265337 |